.. _pid_controller:
|
|
|
|
PID Controller
|
|
==============
|
|
|
|
The PID controller is the main element of the oven. It controls the output of the solid state relais in order to achieve the desired temperature.
|
|
|
|
The PID controller is implemented in the ``pid-controller.c`` file. See the :ref:`pid_code_api` for details.
|
|
|
|
Functional Description
|
|
----------------------
|
|
|
|
The following figure shows the PID controller's structure.
|
|
|
|
.. drawio-image:: pid.drawio
|
|
|
|
The controller is composed of 3 paths. The proportional, the derivate, and the integrator path.
|
|
Compared to a textbook PID controller, this version contains a few additional features.
|
|
|
|
The integrator has a configurable maximum limit of :c:var:`pid_controller.integral_max`. Once this value is reached (plus or minus), the integrator freezes.
|
|
The integrator is also frozen in case the output value is in saturation. This serves as an anti-windup protection.
|
|
|
|
The output value saturates at configurable high and low limits (:c:var:`pid_controller.output_sat_max` and :c:var:`pid_controller.output_sat_min`). The controller instance used for the
|
|
reflow oven's solid state relais output is saturated by software to a limit of 0 to 100.
|
|
|
|
In addition to the above features, the derivate term contains an additional first order low pass filter in order to prevent coupling of high frequency noise amplified by the derivate term.
|
|
The low pass filter is charcterized by its time constant :math:`k_{d\tau}`.
|
|
|
|
Time Continuous Transfer Function
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
The time continous transfer function of the PID controller is
|
|
|
|
.. math:: H_c(s) = \frac{Y_c(s)}{X_c(s)} = k_p + \frac{k_i}{s} + \frac{k_ds}{1+sk_{d\tau}}
|
|
|
|
|
|
Time Discrete Transfer Function
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
The time descrete transfer function which is implemented in the code is derived by converting the time continuous transfer function
|
|
with the bilinear transformation:
|
|
|
|
.. math:: s = \frac{2}{T_s}\cdot \frac{z-1}{z+1}
|
|
|
|
The frequency warping of the bilinear transform can be considered negligible because the PID controller is targetted for low frequency temperature signal data with a maximum far below the nyquist freqency.
|
|
In this area, the mapping of the continuous frequencies to the time descrete can be considered linear.
|
|
|
|
The time discrete transfer function after inserting the bilinear transform is:
|
|
|
|
.. math:: H_d(z) = H_c(s)\bigg|_{s=\frac{2}{T_s}\cdot \frac{z-1}{z+1}} = k_p + \frac{k_i T_s (z+1)}{2(z-1)} + \frac{\frac{2}{T_s}k_d(z-1)}{\left(1+\frac{2k_{d\tau}}{T_s}\right)z+\left(1-\frac{2k_{d\tau}}{T_s}\right)}.
|
|
|
|
Converted to an implementable form:
|
|
|
|
.. math:: H_d(z) = k_p + \frac{k_iT_s(1+ z^{-1})}{2(1-z^{-1})} + \frac{\frac{2}{T_s}k_d(1-z^{-1})}{(1+2k_{d\tau}T_s^{-1})+(1-2k_{d\tau}T_s^{-1})z^{-1}}
|
|
|
|
This function can be splitted in the three individual parts of the PID controller:
|
|
|
|
.. math:: H_{d1}(z) = k_p
|
|
.. math:: H_{d2}(z) = \frac{k_iT_s(1+ z^{-1})}{2(1-z^{-1})}
|
|
.. math:: H_{d3}(z) = \frac{\frac{2}{T_s}k_d(1-z^{-1})}{(1+2k_{d\tau}T_s^{-1})+(1-2k_{d\tau}T_s^{-1})z^{-1}}
|
|
|
|
The individual time domain difference equations :math:`y_i[n] = \mathcal{Z}^{-1}\left\lbrace H_{di} * X(z)\right\rbrace` that are implemented in software are:
|
|
|
|
.. math:: y_1[n] = k_p x[n]
|
|
.. math:: y_2[n] = \underbrace{\frac{k_iT_s}{2}}_{k_{i_t}} \left( x[n] + x[n-1]\right) + y_2[n-1]
|
|
.. math:: y_3[n] = \underbrace{\frac{2k_{d}}{2k_{d\tau} + T_s}}_{k_{d_t}}\left( x[n] - x[n-1] \right) + \underbrace{\frac{2k_{d\tau} - T_s}{2k_{d\tau} + T_s}}_{\overline{k_{d_t}}} y_3[n-1]
|
|
|
|
The final output value is the sum of all three terms:
|
|
|
|
.. math:: y[n] = \sum_{i=1}^{3} y_i[n]
|
|
|
|
.. _pid_code_api:
|
|
|
|
PID Controller Code API
|
|
-----------------------
|
|
|
|
.. doxygengroup:: pid-controller
|
|
:project: Reflow Controller Firmware |